Simoprime by Simosynergy
+
  • Simoprime by Simosynergy

Share to

Simoprime by Simosynergy

The SIMOPRIME type circuit breaker switchgear is a factory-assembled, drawer-type switchgear suitable for indoor installation, compliant with IEC 62271-200 and VDE 0671-200 standards.

After-sales Hotline

Belonging Category

Keywords

  • Product Description
  • Product Introduction

    The SIMOPRIME type circuit breaker switchgear is a factory-assembled, withdrawable switchgear suitable for indoor installation, compliant with IEC 62271-200 and VDE 0671-200 standards.

    Continuous Operation Category: LSC 2B

    Partition Category: PM

    - Internal Arc Classification: IAC A FLR, Isc 40kA

    - Arc Duration: 1 or 0.1 seconds

    SIMOPRIME switchgear type: maximum rated value of 17.5kV/40 kA/3600 A

     

    Typical Applications
    SIMOPRIME circuit breaker switchgear can be used for transformers and distribution substations, such as:
    Power System Supply

    Power Supply Companies

    Industry

    Cement Industry   
    Automotive Industry   
    Metallurgical Industry   
    Rolling Mills   
    Mining Industry   
    Food and Beverage Industry   
    Chemical Industry   
    Petroleum Industry   
    Pipeline Facilities   
    Offshore Facilities   
    Electrochemical Plants   
    Pharmaceutical Plants   
    Commercial Buildings   
    High-rise Buildings   
    Other Applications   
    Renewable Energy Supply Devices   
    Ignition Preheating Panel   
    Rail Transit Power Systems

    Electrical Data of SIMOPRIME (Maximum Values)
    Rated Value≥7.2kV12kV15kV17.5kV
    Rated Voltage7.2kV12kV15kV17.5kV
    Rated Frequency50/60Hz50/60Hz50/60Hz50/60Hz
    Rated Short-time Power Frequency Withstand Voltage20kV(1)28kV(1)35kV(1)38kV
    Rated Lightning Impulse Withstand Voltage60kV75kV(3)95kV95kV
    Rated Short-time Withstand Current40kA40kA40kA40kA
    Rated Peak Withstand Current100/104kA100/104kA100/104kA100/104kA
    Rated Short-circuit Breaking Current40kA40kA40kA40kA
    Rated Short-circuit Making Current100/104kA100/104kA100/104kA100/104kA
    Rated Busbar Normal Current

    3600A

    4000A(4)

    3600A

    4000A(4)

    3600A

    4000A(4)

    3600A

    4000A

    Rated Feeder Normal Current    
    Using Circuit Breaker

    3600A

    4000A(4)

    400A(2)

    3600A

    4000A(4)

    400A(2)

    3600A

    4000A(4)

    -

    3600A

    4000A

    -

     